Skip to content
VoltAire HIX025B HIX Cross Flow heat exchanger (representative product photo — actual unit photography forthcoming)

HIX Cross Flow

HIX025B

25 W/°F hix cross flow air-to-air heat exchanger. 48VDC input.

Starting Price

$1,817

Integrator pricing available • Volume discounts on 4+ units

1 In Stock
Cabinet finish
  • Hentzen P2234WPC-2 Off White
  • RAL 7035 Light Gray
  • Aluminum Quoted
  • Stainless Steel (Type 4X) Quoted
  • Special / custom paint Quoted

Ordering as HIX025BW* — the * is VoltAire’s engineering revision, set at order review.

1 in stock — ships by tomorrow.

1

Super Cool Coverage — 2 years of coverage, 30-day returns, no restocking fee. Terms

NEMA 4 / 4X UL Recognized (UL 1995) GR-487 BABA documentation on request −40°F to 158°F Made in USA

Technical Specifications

HIX025B at a glance

Capacity
25 W/°F (watts removed per °F of cabinet-to-ambient ΔT)
Series
HIX Cross Flow
Flow Configuration
Cross Flow
Voltage
48VDC
Fan Power (typical)
72 W
Sound Level
61 dBa @ 3 m
Outer Dimensions (W × H × D)
12.0 × 22.8 × 5.3″
Return Opening (W × H)
4.37 × 6.50″
Supply Opening (W × H)
3.97 × 8.06″
Mounting Holes
10 × Ø0.31″ (M6) on a 11.84 × 22.84″ template (drawing, BC0117F p. 3)
Weight
20.1 lbs
Operating Range
−40°F to 158°F (−40°C to 70°C)

Specifications subject to change. Always verify against the current spec sheet before final design submittal.

Model Number Decoded

What does HIX025B mean?

H I X 0 2 5 B
  • H = Heat exchanger
  • I = Industrial series (industrial / utility)
  • X = Cross Flow configuration
  • 025 = 25 W/°F capacity designation
  • B = 48VDC input

Where HIX025B Fits

Best applications for this model

HIX025B is sized for cabinets where the internal heat load is in the range that 25 W/°F can move at your available temperature differential. As a quick rule of thumb, multiply 25 by your ambient-to-target ΔT to get the maximum heat load (in watts) this unit can handle. For example, at a 20°F ΔT this model removes 500W; at a 30°F ΔT, 750W.

Watch: Cross Flow vs. Counter Flow

Common use cases

Outdoor telecom RTUs, fiber distribution cabinets, small-cell shelters, pipeline SCADA panels.

Voltage fit

Direct connection to −48V telecom plant . No inverter required. Battery-resilient cooling.

Ready to spec HIX025B?

Quotes returned same day. Integrator pricing on request. Built and shipped from Orlando, FL with US-stocked replacement parts.